绝缘子序号N(自地线侧数 |
绝缘子串分布电压值Ui KV |
||||||||
35KV线路 | 110KV线路 | 220KV线路 | |||||||
2片/串 | 3片/串 | 4片/串 | 6片/串 | 7片/串 | 8片/串 | 12片/串 | 13片/串 | 14片/串 | |
1 | 10.0 | 6.0 | 4.0 | 10.0 | 9.0 | 8.0 | 6.0 | 7.5 | 8.0 |
2 | 10.0 | 5.0 | 3.5 | 7.0 | 6.0 | 5.0 | 7.0 | 6.5 | 6.0 |
3 | 9.0 | 4.8 | 8.0 | 5.0 | 5.0 | 7.0 | 6.0 | 6.5 | |
4 | 8.0 | 9.0 | 4.0 | 4.0 | 7.0 | 6.0 | 5.0 | ||
5 | 11.0 | 8.5 | 6.5 | 8.0 | 6.0 | 5.0 | |||
6 | 19.0 | 10.0 | 8.0 | 9.0 | 6.9 | 5.0 | |||
7 | 17.0 | 10.0 | 10.0 | 7.1 | 5.0 | ||||
8 | 17.0 | 11.0 | 7.5 | 6.0 | |||||
9 | 13.0 | 9.0 | 6.5 | ||||||
10 | 15.0 | 12.1 | 7.0 | ||||||
11 | 16.0 | 12.1 | 9.0 | ||||||
12 | 18.0 | 18.2 | 12.5 | ||||||
13 | 22.5 | 16.0 | |||||||
14 | 31.0 | ||||||||
总计 | 20 | 20 | 20.3 | 64 | 64 | 63.5 | 127 | 127.4 | 128 |
额定电压(KV) | 有效长度(M) | 工频耐受电压 | 试验时间(mim) | 试验结果 | |
标准值(KV) | 试验值(KV) | ||||
35 | 2.5 | 95 | 95 | 1 | 合格 |
66-110 | 3 | 220 | 220 | 1 | 合格 |
220 | 3.5 | 440 | 440 | 1 | 合格 |
330 | 4 | 380 | 380 | 5 | 合格 |
500 | 5 | 580 | 580 | 5 | 合格 |
上一篇:SF6气体回收装置的简单配置